	Nominal frequency: 50 to 60 Hz 
- 
	Power consumption in the circuit path: 0.1 VA at IN =1A 
- 
	Thermal load capacity of current circuit:
 Surge current (half-wave) 250x IN
 for 1s 100x IN
 for 10s 30x IN
 continuous 4x IN
 
- 
	Output relay:
 Switch-on current: 20A
 Nominal current: 5A
 Max. contact rating:
 1250 VA/DC; 120W/DC, ohmic
 500VA/AC; 75W/DC, inductive
 
- 
	Trip parameters:
 I > 0.5-2x IN
 I > 1-15x IN
 tI > 0-100s
 tI > 0-2.5s
 
- 
	LED indicators:
 "ON" for ready
 I> and I>> starting (flashing)
 I> and I>> tripping (permanently On)
 
- 
	Controls:
 "TEST" button to initiate the self-test
 6 potentiometers for adjusting operate and trip times
 8 DIP switches for adjusting the characteristics
 Adjustments for time factors and nominal data
 
- 
	Inputs/outputs: 4mm safety sockets 
- 
	The integrated interface RS 485 is suitable for setting the relay parameters. It is also possible to store and transmit measured relay values to and from the PC. Optical signal transmission guarantees galvanic isolation. 
- 
	Indicators of the interface:
 1. LED green = operation indicator
 2. LEDs green = data transfer
 
- 
	Dimensions: 297 x 228 x 125mm (HxWxD) 
- 
	Weight: 1kg